Huawei Inverter Configuration Guide
How to connect Huawei inverters to Sourceful Zap via Modbus TCP or Modbus RTU (RS485).
The Sourceful Zap supports two connection methods for Huawei inverters: Modbus TCP (via SDongle and network) and Modbus RTU (via RS485 direct wiring). These are mutually exclusive — the dongle must be disconnected when using RTU.
Compatible Models
-
SUN2000 3-10KTL M0/M1 -
SUN2000 12-25K MB0 -
SUN2000 5-12K MAP0
Modbus TCP (via SDongle)
Prerequisites
Hardware Requirements
-
Mobile device
-
iPhone with iOS 10.0 or later
-
Android with Android 4.0 or later
-
-
Huawei
SDongle -
Internet connectivity
-
WiFi capability
Software Requirements
-
SUN2000 App (version 3.2.00.015 or later)
-
Available from
Huawei AppGallery
Configuration Process
Initial Setup
-
Install SUN2000 App from
Huawei AppGallery -
Ensure SDongle remains powered throughout configuration
Connection Setup
-
Open
SUN2000App -
Select
Connect→WLAN -
Choose inverter's WiFi network
-
Enter password:
-
First login:
Changeme -
Change password after initial login
-
Modbus TCP Configuration
-
Login as installer (default password: 00000a )
-
Navigate to: Settings → Communication Configuration → Dongle Parameter Settings → Modbus-TCP
-
Select appropriate access mode:
-
Unrestricted: Allows all LAN devices (one at a time) -
Restricted: Requires setting trusted IP address -
Disabled: No Modbus access
-
Important Notes
-
Configuration settings persist through power cycles
-
New inverters require fresh configuration
-
SDonglereplacement doesn't require reconfiguration -
Keep
SDonglepowered during configuration process
To verify your Modbus TCP connection is working, see How do I know if Modbus TCP is activated on my inverter?
Modbus RTU (via RS485)
Note: Modbus RTU requires disconnecting the SDongle. With the dongle disconnected, the connection to FusionSolar is lost. Do not reconnect the dongle while the system is in operation.
Prerequisites
-
Sourceful Zap
-
Shielded twisted pair cable
-
Only one inverter is supported — the inverter must not be cascaded with another inverter. If such a connection exists, disconnect it before installation.
Wiring
Zap Side

Strip one end of the twisted pair cable. Use the green pair:
-
Connect green wire to the Zap A+ terminal
-
Connect green/white wire to the Zap B- terminal
Inverter Side

Ensure the dongle is disconnected before connecting.
Connect to the COM port on the bottom of the inverter:
-
Green wire → terminal 1 (485A1-1)
-
Green/white wire → terminal 3 (485B1-1)
Troubleshooting
Modbus TCP
If Modbus settings are not visible:
-
Check firmware versions
-
Update app if necessary
-
Verify
SDonglecompatibility
Connection Problems
If unable to connect:
-
Ensure SDongle is powered
-
Stay within WiFi range
-
Verify correct password
Access Issues
If experiencing access problems:
-
Check IP restrictions if enabled
-
Verify only one client is connecting
-
Confirm network settings are correct
Modbus RTU
If RS485 communication is not working:
-
Verify the dongle is disconnected
-
Ensure the inverter is not cascaded with another inverter
-
Double-check COM port terminal connections (terminal 1 and 3)
-
Ensure all cable connections are firmly seated