Prerequisites
Required Items
WiFi-capable device (smartphone, tablet, or laptop)
Inverter
serial numberWPA2-PSKpassword (located on inverter label)Installerrights for certain settings
Configuration Process
Initial Connection
Choose one of these connection methods:
WiFi Connection
Find network named
SMA19xxxxxxxUse IP address:
192.168.12.3
Ethernet Connection
Connect via ethernet cable
Use IP address:
169.254.12.3
Settings Configuration
Open web browser
Enter appropriate
IPaddress based on connection methodLog in as
InstallerNavigate to
Device ParametersSelect
Edit Parameters
Modbus Setup
Navigate to
ModbussettingsEnable the Modbus feature
Enable
TCP serverLeave the port as
502
Grid Connection Configuration
For standard models:
Go to
System and device controlFind
Grid connection pointChange
Operating mode of active power limitationtoExternal
For SBx.x-1AV40/41 models:
Locate
Operating mode active power settingSet to
External active power setpoint
Finalizing Changes
Always click
Save Allafter making modificationsWait for changes to be applied
Troubleshooting
Modbus Setting Issues
If unable to change Modbus settings:
Contact your installer
Check if settings are locked by
SMA Grid GuardVerify
installeraccess rights
Connection Problems
If experiencing connection issues:
Verify correct WiFi network selection
Double-check
IPaddressEnsure you're within range of the inverter
Missing Settings
If settings are not visible:
Verify your model number
Check for alternative setting names
Confirm
installeraccess level
Testing Connectivity (advanced)
After enabling Modbus TCP on your SMA inverter, you should verify that the connection is functioning correctly. You can follow our testing guide to confirm the connection. For SMA inverters, use the default Modbus port 502. The Unit ID is typically set to 3, which differs from many other manufacturers. Make sure you've completed all the grid connection configuration steps before testing, as these settings can affect Modbus communication.