Fronius - Activate Modbus TCP

Fronius inverters can be configured for Modbus TCP  in two different ways, depending on your model. This guide covers both standard Fronius inverters with Datalogger  and GEN24  models.

Prerequisites

Access level requirements vary by model:

  • Standard Fronius with DataloggerAdmin  credentials
  • GEN24Technician  account or Customer  account with support assistance
  • Network connectivity
  • Web browser

Configuration for Standard Fronius with Datalogger

Initial Connection

  1. Connect to inverter's WiFi access point:
    • Locate network name containing Datalogger ID  (240.xxxxx or 239)
    • Use default WiFi password: 12345678
    • Access web interface at 192.168.250.181  (or assigned IP)

Modbus Configuration

  1. Log in with Admin  credentials
  2. Navigate to Modbus  settings
  3. Configure the following:
    • Set "Data export via Modbus" to tcp
    • Change "Sunspec Model type" to float
  4. Save configuration

Control Priority Setup

  1. Access DNO Editor
  2. Set "Controlling via Modbus" to priority 1
  3. Adjust priority order if needed
  4. Save changes

Configuration for GEN24 Series

Initial Access Setup

  1. Connect to inverter WiFi (password: 12345678 )
  2. Navigate to 192.168.250.181
  3. Access System  → Support
  4. Enable both:
    • Remote Access
    • Support User

Modbus Configuration (Technician Access)

  1. Navigate to Communication  → Modbus
  2. Enable "Control via Modbus TCP"
  3. Set "SunSpec Model Type" to float
  4. Enable "Allow Control"

Control Priority Setup

  1. Access Safety and Grid Regulations
  2. Set Modbus Control  to highest priority
  3. Save all changes

Important Notes

  • Password management varies by model type
  • Multiple inverters require individual configuration
  • Document settings for each unit

Troubleshooting

Access Issues

For login problems:

  1. Contact support with model and serial numbers for password resets
  2. Verify network settings
  3. Double-check IP addresses

Configuration Problems

If experiencing issues:

  1. For GEN24  models, consult installer or Fronius support
  2. Verify all settings are saved properly
  3. Check network connectivity

Testing connectivity (advanced)

After configuring Modbus TCP on your Fronius inverter, it's important to verify that the connection is working properly. You can follow our testing guide to confirm the connection. For Fronius inverters, use the default Modbus port 502. The Unit ID is typically set to 1, but you might need to check your specific configuration if this doesn't work. Remember that both standard and GEN24 models use the same Modbus TCP port and Unit ID conventions.