SMA - Activate Modbus TCP
The following guide describes how to configure the Modbus TCP
settings for SMA inverters and how to test the connection.
Prerequisites
Required Items
- WiFi-capable device (smartphone, tablet, or laptop)
- Inverter
serial number
WPA2-PSK
password (located on inverter label)Installer
rights for certain settings
Configuration Process
Initial Connection
Choose one of these connection methods:
WiFi Connection
- Find network named
SMA19xxxxxxx
- Use IP address:
192.168.12.3
Ethernet Connection
- Connect via ethernet cable
- Use IP address:
169.254.12.3
Settings Configuration
- Open web browser
- Enter appropriate
IP
address based on connection method - Log in as
Installer
- Navigate to
Device Parameters
- Select
Edit Parameters
Modbus Setup
- Navigate to
Modbus
settings - Enable the Modbus feature
- Enable
TCP server
- Leave the port as
502
Grid Connection Configuration
For standard models:
- Go to
System and device control
- Find
Grid connection point
- Change
Operating mode of active power limitation
toExternal
For SBx.x-1AV40/41
models:
- Locate
Operating mode active power setting
- Set to
External active power setpoint
Finalizing Changes
- Always click
Save All
after making modifications - Wait for changes to be applied
Troubleshooting
Modbus Setting Issues
If unable to change Modbus settings:
- Contact your installer
- Check if settings are locked by
SMA Grid Guard
- Verify
installer
access rights
Connection Problems
If experiencing connection issues:
- Verify correct WiFi network selection
- Double-check
IP
address - Ensure you're within range of the inverter
Missing Settings
If settings are not visible:
- Verify your model number
- Check for alternative setting names
- Confirm
installer
access level
Testing Connectivity (advanced)
After enabling Modbus TCP on your SMA inverter, you should verify that the connection is functioning correctly. You can follow our testing guide to confirm the connection. For SMA inverters, use the default Modbus port 502. The Unit ID is typically set to 3, which differs from many other manufacturers. Make sure you've completed all the grid connection configuration steps before testing, as these settings can affect Modbus communication.